Transformer:
EMF
of Primary Winding/Phase, Ep = 4.44NPfφM Volts
EMF
of Secondary Winding/Phase, ES = 4.44NSfφM Volts
Transformation
Ratio , k or a = Ep / ES = Np / NS = IS / IP
No Load Loss, ωO =
Vi IO CosφO
Working
Component, IW = IO CosφO
Magnetizing
Component, Iµ = IO SinφO
No
load Power factor, CosφO
= ωO / Vi IO
Condition
for Maximum Efficiency is: Core Loss =
Copper Loss
Hysteresis
Loss, Ph = Kh f Bm 1.6 (Watt) [Here, Kh = Constant, Bm
= Max. Flux Density, f= Frequency]
Eddy
current loss, Pe = Ke f2 Bm2
t2 (Watt) [Here, Ke =
Constant, Bm = Max. Flux Density, f= Frequency, t = Thickness of
lamination sheet]
KVAMAX
= KVARATED √(Core Loss/F.L Copper Loss)
Full
load copper loss 400W, in half load copper loss is: 400x (1/2)2
Auto Transformer:
Transformed
Power = Delivered Power x (1-a)
Conducted
Power = Delivered Power – Transformed Power